Application

The RCS-974 relay is a non-electrical quantity protection used for transformers and generators. The non-electrical quantity can be configured as thermal, gas, oil temperature, winding temperature, pressure, oil level and so on. It is fully compatible with IEC 61850 communication.


 
Functional Block Diagram

Functions
l      Non-electrical quantity protection. (26, 63, NE)
l      Breaker failure protection. (50BF)
l      Gas alarm and tripping function.
l      Pole discrepancy function.
l      Circuit breaker monitoring.
l      CT failure detection logic.
l      Operating circuit supervision.
l      Current drift auto adjustment.
l      Self diagnostic test.
l      GPS clock synchronization.
l      Fault Recorder.
l      128 Event reports.
l      High resolution oscillography of last 24 oscillograms
      (Compatible with international COMTRADE format)
l      Rear communication ports: Ethernet (Optional) or 2 RS-485 with IEC 60870-5-103 protocol,
      1 RS-485 with clock synchronization, 1 RS-232 or RS-485 with printer.
l       Front communication port: 1 RS-232 for testing and setting.

Features
l      Seven (7) channels of non-electrical quantity inputs are for signaling. Five (5) channels of non-electrical quantity inputs are for instantaneous tripping. Three (3) channels of non-electrical quantity inputs are for tripping with time delay.
  

l      Innovative technology to prevent any undesired trip caused by any component failure is adopted. The relay has two independent data acquisition paths, one for a fault detector and the other for protection and its logic. Tripping outputs are supervised by the fault detector to prevent a mal-operation.

l      The connector type can be selected as connectorized wiring connector and crimp terminal connector. The unique connectorized wiring connectors from the relay rear panel to the terminal blocks on the rack or cabinet makes the on-site commissioning and replacement much easier than when you do the commissioning using the traditional screw terminals on the rear panel.

l      On the premise of 24 samples per cycle, all data measurement, calculation and logic discrimination could be done within one sampling period. The event recording and protection logic calculation are completed simultaneously.

l      The relay provides GPS clock synchronization, including second pulse, minute pulse and IRIG-B synchronization.

l      The format of event report is compatible with international COMTRADE file.

l      The relay is compatible with multiple protocols- IEC61850 and IEC 60870-5-103. It provides networking interface such as RS485, RS232 and Ethernet port.