Application
The RCS-9613C relay is a current differential protection, control and monitoring unit with auto-reclosing used for distribution feeders. It is fully compatible with IEC 61850 communication.
Functions
l Current differential protection. (87F)
l Three-level overcurrent protection. (50P, 51P)
l Three-level directional overcurrent protection. (67P)
l Three-level zero sequence overcurrent protection. (50G, 51G)
l Under frequency protection. (81)
l Frequency rate-of-change element. (7F)
l Switch-on-to-fault (SOFT) logic.
l Overload protection.
l Synchronism check. (25)
l Auto-reclosing (three-pole). (79)
l Eight (8) binary inputs.
l Circuit breaker control.
l Fourteen (14) analog quantity measurements.
l Four (4) pulse accumulating inputs.
l Circuit breaker monitoring.
l CT failure detection logic.
l VT failure detection logic.
l Line voltage failure supervision.
l Voltage and current drift auto adjustment.
l Self diagnostic test.
l GPS clock synchronization.
l Fault Recorder.
l 64 tripping reports and 256 SOE (Sequence of Events) records.
l High resolution oscillography of last 8 oscillograms (compatible with international COMTRADE format)
l Rear communication ports: Ethernet (Optional), 2 RS-485 or 2 Worldfip bus interfaces with IEC 60870-5-103 protocol, 1 RS-485 with clock synchronization, 1 RS-485 with printer.
Features
l Definite time and inverse time characteristics of overcurrent protection are both provided.
l Overcurrent protection could be supervised by voltage elements.
l Under frequency protection that could be supervised by rate-of-change element would shed loads before out-of-step.
l The RCS-9613 relay constantly measures a large mount of analog quantities, such as phase voltage, phase-to-phase voltage, neutral voltage, phase current, neutral current, active power, reactive power, power factor and frequency.
l The relay can monitor the status and record the number of switching times of the circuit breaker.
l On the premise of 24 samples per cycle, all data measurement, calculation and logic discrimination could be done within one sampling period. The event recording and protection logic calculation are completed simultaneously.
l The relay provides GPS clock synchronization, including second pulse and IRIG-B synchronization.
l The HMI interface with a LCD and a 9-button keypad on the front panel is friendly to users.
l The format of event report is compatible with international COMTRADE file.
l The relay is equipped with Ethernet ports with the IEC 61850 protocol and RS-485 ports and IEC 60870-5-103 protocol.
|